60 Hz Ambient Airflow Sound Pressure Levels Exhaust Back
SA Enclosure 2 Breaker Capability* Rate dBA @ Full Load Pressure
ekW kVA PP/SB °C °F m
3
/s cfm 1 m 7 m 15 m in/H
2
O kPa
600 750 SB 49 120 9.6 20,341 85.7 76.6 70.6 12.45 3.10
545 681 PP 48 118 9.6 20,341 85.2 76.1 70.1 6.02 1.50
550 688 SB 53 127 9.6 20,341 85.2 76.1 70.1 6.22 1.55
500 625 PP 52 126 9.6 20,341 84.8 75.7 69.7 5.30 1.32
ENCLOSURES
LEHE4763-02 2
*Ambient measured with Caterpillar Extended Life Coolant
*Ambient measured with Caterpillar Extended Life Coolant
ENCLOSURE OPERATING CHARACTERISTICS
50 Hz Ambient Airflow Sound Pressure Levels Exhaust Back
SA Enclosure Capability* Rate dBA @ Full Load Pressure
ekW kVA PP/SB °C °F m
3
/s cfm 1 m 7 m 15 m in/H
2
O kPa
560 700 SB 52 126 7.1 15,044 84.7 76.4 70.4 4.82 1.20
508 635 PP 52 126 7.1 15,044 84.5 76.5 70.5 3.68 0.92
520 650 SB 56 133 7.1 15,044 84.6 76.5 70.5 3.90 0.97
473 591 PP 55 131 7.1 15,044 84.4 76.5 70.5 3.08 0.77
480 600 SB 59 138 7.1 15,044 84.4 76.5 70.5 3.19 0.80
436 545 PP 58 136 7.1 15,044 84.3 76.5 70.5 2.56 0.64
440 550 SB 62 144 7.1 15,044 84.3 76.5 70.5 2.61 0.65
400 500 PP 61 142 7.1 15,044 84.1 76.4 70.4 2.14 0.53
*Ambient measured with Caterpillar Extended Life Coolant
60 Hz Ambient Airflow Sound Pressure Levels Exhaust Back
SA Enclosure 1 Breaker Capability* Rate dBA @ Full Load Pressure
ekW kVA PP/SB °C °F m
3
/s cfm 1 m 7 m 15 m in/H
2
O kPa
600 750 SB 50 122 9.8 20,765 85.7 76.6 70.6 12.45 3.10
545 681 PP 48 118 9.8 20,765 85.2 76.1 70.1 6.02 1.50
550 688 SB 54 129 9.8 20,765 85.2 76.1 70.1 6.22 1.55
500 625 PP 51 124 9.8 20,765 84.8 75.7 69.7 5.30 1.32